Viessmann Boiler Equipment & Error Codes

Technical specifications, platform control notes, and complete error code lookup table for Viessmann boilers.

Platform & Control Notes

Vitodens 100-W / 200-W / 222-F fault codes. These models share the same Viessmann control platform and fault code set. Reset is via the 'R' button on the control panel. Codes starting with letters (E_, F_, B_) appear on the boiler display. Some additional 'detailed codes' (plain numbers) appear in the service menu under coding address 38:XX and indicate hold/wait states rather than hard faults.

Model Families & Platforms

  • Vitodens 100-W (Compact residential condensing boiler)
  • Vitodens 200-W (Advanced residential condensing boiler)
  • Vitodens 222-F (Floor-standing condensing boiler with storage tank)

Diagnostic Characteristics & Common Service Topics

Viessmann boilers utilize specific display codes and safety lockouts to protect the heat exchanger, combustion system, and hydronic loop. Everyday issues like pressure loss, flame sensing errors, or circulator faults trigger specific responses depending on the controller generation.

Sample Fault Code Summaries from Vault Records
CodeMeaningAction Required
30Burner blocked — short circuit on boiler water temperature sensor.Sensor diagnosis/replacement is a tech task. Call a pro if the boiler stays blocked.
38Burner blocked — boiler water temperature sensor cable broken (open circuit).Sensor diagnosis/replacement is a tech task. Call a pro if the boiler stays blocked.
B0Burner blocked — flue gas temperature sensor shorted out.Flue-sensor diagnosis is a pro task; call a tech to check the sensor and wiring.
B8Burner blocked — flue gas temperature sensor cable broken (open circuit).Flue-sensor diagnosis is a pro task; call a tech to check the sensor and wiring.
E1Ionization current too high during calibration.Combustion/calibration fault — call a pro to check the ionization electrode gap and combustion air quality. Press 'R' to reset.
E2Heating water flow rate too low during calibration.Check boiler pump flow and ensure adequate circulation volume. Remove scaling or blockage. Press 'R' to reset.
E3Heat transfer too low during calibration — temperature limiter caused shutdown.Ensure adequate heat transfer and water flow. Press 'R' to reset. Repeated faults need a pro.
E5Burner blocked — flame amplifier fault.Call a pro — control unit likely needs replacement.